Three Phase Dry Type 3D Core Distribution Transformer
3 Dimension (3D) Wound Cores” are made from three identical single-core frames of trapezoidal silicon steel tape, wound into a compact triangular structure that eliminates air gaps. This innovative design ensures uniform flux flow, reduces total core weight, lowers no-load loss by 20-25%, and decreases excitation current by 50%, significantly minimizing reactive loss and improving the transformer’s power factor (Cos-phi).
- Description
- Additional information
- Reviews (0)
- ADDITIONAL PICTURE
- SERVICES CONDITIONS
- Store Policies
- Inquiries
Description
Our Dry Type Transformers, designed for up to 36 kV and 10,000 kVA applications, feature high-efficiency, fire-resistant, and eco-friendly insulation with Class F or H ratings, copper or aluminum windings, natural or forced air cooling, IP00–IP54 protection, compliance with IEC, IEEE, and local standards, and advanced safety features like thermal sensors and short-circuit resistance, making them ideal for commercial, industrial, and infrastructure applications.
Dry Type Transformer (20kV System Voltage)
Phase | Capacity | Impedance | No Load Loss | Load Lose | Total Loss | Transformer Dimension | Total Weight Approx | Enclosure Dimension |
---|---|---|---|---|---|---|---|---|
kVa | % | % | Watt | Watt | mm | kg | mm | |
3 | 630 | 4 | 1600 | 8800 | 1040 | 1700*1300*1692 | 2650 | 2375*1712*2422 |
3 | 800 | 5 | 1900 | 9500 | 11400 | 1700*1500*1695 | 2900 | |
3 | 1000 | 5 | 2350 | 11000 | 13350 | 1800*1500*1782 | 3100 | |
3 | 1250 | 5.5 | 2500 | 15800 | 18300 | 2000*1650*2125 | 3600 | 2650*1960*2570 |
3 | 1600 | 6 | 2900 | 18200 | 21100 | 2060*1650*2115 | 4070 | |
3 | 2000 | 7 | 3400 | 23000 | 26400 | 2290*1750*2085 | 5410 | 2910*1960*2570 |
3 | 2500 | 7 | 4200 | 24700 | 28900 | 2400*1750*2014 | 5580 |
Dry Type Transformer (20kV System Voltage)
Phase | Capacity | Impedance | No Load Loss | Load Lose | Total Loss | Transformer Dimension | Total Weight Approx | Enclosure Dimension |
---|---|---|---|---|---|---|---|---|
kVa | % | % | Watt | Watt | mm | kg | mm | |
3 | 630 | 4 | 1600 | 8800 | 1040 | 1600*1300*1911 | 2050 | 2400*1765*2670 |
3 | 800 | 5 | 1900 | 9500 | 11400 | 1680*1500*2042 | 2400 | |
3 | 1000 | 5 | 2350 | 11000 | 13350 | 1690*1500*2195 | 2650 | |
3 | 1250 | 5.5 | 2500 | 15800 | 18300 | 1735*1500*2195 | 3070 | 2560*1710*2832 |
3 | 1600 | 6 | 2900 | 18200 | 21100 | 1900*1500*2277 | 3850 | |
3 | 2000 | 7 | 3400 | 23000 | 26400 | 2100*1900*2364 | 4300 | 2810*2115*2823 |
3 | 2500 | 7 | 4200 | 24700 | 28900 | 2300*1902*2420 | 4720 |
Additional information
Weight | 5580 kg |
---|---|
Dimensions | 360 × 220 × 240 cm |
Capacity (kVa) | 200kVa, 250kVa, 315kVa, 400kVa, 500kVa, 630kVa, 800kVa, 1000kVa, 1250kVa, 1600kVa, 2000kVa, 2500kVa, 3000kVa, 3150kVa, 3500kVa, 4000kVa |
Cooling Method | Dry-type Transformer |
Be the first to review “Three Phase Dry Type 3D Core Distribution Transformer” Cancel reply
Oil Immersed Distribution Transformer
Transformer normal service conditions
The height above the sea level is below 1000m;
Highest air temperature +40ºC;
Highest daily average air temperature+30ºC;
Highest annual average air temperature +20ºC;
Lowest outdoor air temperature -5ºC.
(defines in detail when transformer in special service conditions )